Pressure Sensor & Switch

LED Digital Pressure Sensor

RoHS2 Compliant

LED with good visibility for vacuum switch display

Advantages

To improve visibility, an LED display is adopted
for the vacuum switch.

LED displays are used for set-up pressure and working pressure.

2 points signal output type and 1point signal output with 1 analog output type is available.

Selection by applications is possible. A connector wiring realize easy layout.

Output detection accuracy is enhanced by the use of semiconductor switch.

Specifications

General spec.

Current consumption 40mA or less
Pressure detection Diffused metaloxide semiconductive pressure transducer
Operating pressure range -100~0kPa
Pressure setting range -99~0kPa
Proof pressure 0.2MPa
Operating temperature range 0~50°C (No freezing)
Operating humidity range 35~85% RH (No dew condensation)
Power supply 12~24VDC ±10%, Ripple (P-P) 10% or less
Protective structure IEC standard IP40 equiv.
Operating accuracy ±3% F.S. or less (at Ta=25°C)
Response About 2msec
Indication 0 ~ -99kPa (2-digit red LED display)
Sampling rate About 4 times/sec
Indication accuracy ≦±3% F.S. ±2 digits
Sensor resolution 1 digit

2-point switch outputs specifications

Factory default pressure -50kPa(SW1), -10kPa(SW2)
No. of pressure setting 2
Hysteresis Fixed (2% F.S. or less)
Switch output NPN open collector/30V 80mA or less (Residual voltage:0.8V or less)/PNP open collector/30V 80mA or less (Residual voltage:0.8V or less)
Operation indicator SW1:Red LED turns on when pressure is above the setting. SW2:Green LED turns on when pressure is above the setting.
Function 1. MODE selector switch (ME or S1 or S2), 2. S1 setting trimmer (2/3-turn trimmer), 3. S2 setting trimmer (2/3-turn trimmer)

Analog output type specifications

Factory default pressure -50kPa
No. of pressure setting 1
Hysteresis Variable (about 0 ~15%F.S. max.)
Switch output NPN open collector/30V 80mA or less (Residual voltage:0.8V or less)/PNP open collector/30V 80mA or less (Residual voltage:0.8V or less)
Analog output voltage 1~5V
Analog output Zero-point voltage 1 ±0.1V
Analog output Span voltage 4 ±0.1V
Analog output current 1mA max. (load resistance min.5kΩ)
Analog output LIN/HYS ±0.5% F.S. or less (at Ta=25℃)
Operation indicator Red LED turns on when pressure is above setting
Function 1. MODE selector switch (ME or SW), 2. SW setting trimmer (2/3-turn trimmer), 3. HYS setting trimmer (about 0 ~15% of set value)

Port size

Tube size

mm size (mm) φ4, φ6, φ8

Thread size

Metric female thread M5x0.8

Circuit Diagram

Type & Price list

Detailed Safety Instructions

Caution

1.When setting the pressure and differential response, use a small screwdriver and gently turn the trimmer within its rotation range without applying excessive force. Applying excessive force may cause damage to the trimmer and to the circuit board.

2.To mount the sensor body, use the mounting through holes for M2.5 screws and tighten them with the tightening torque 0.3 to 0.31Nm referring to "2. How to fix body" in the instructions.

3.If other devices are connected to the same power supply as this sensor, and the SW output terminal is short-circuited with minus (-) terminal by a load operation test switch or the like while the minus (-) terminal (COM) is disconnected, the reverse current will flow to switch output circuit and the sensor will be damaged. When using this type of circuit, install a diode to prevent reverse current on the minus (-) side power supply line or on the SW output line in the direction shown in the following figure.

Inquiries about this product

It is also possible to suggest products suitable for various conditions such as applications and functions. Please feel free to contact us or visit the nearest sales office.